Alarm Panle – Fire 8 Zone MAG8P (Teletek)
- Brand
- Teletek
- Code
- 5498
- In stock
- On order
> Zones: 8 fixed conventional zones > Detectors per Zone: Up to 32 detectors (including SensoMAG series) > Call Points: Unlimited per zone > Siren Outputs: 2 monitored 24V DC outputs, 0.5A each > Relays: 1 fire relay, 1 fault relay (volt-free, 500mA @ 24V) > Main: ~230V AC ±10% > Auxiliary: 24V DC…
Prices and availability are confirmed with a quote.
Description
> Zones: 8 fixed conventional zones
> Detectors per Zone: Up to 32 detectors (including SensoMAG series)
> Call Points: Unlimited per zone
> Siren Outputs: 2 monitored 24V DC outputs, 0.5A each
> Relays: 1 fire relay, 1 fault relay (volt-free, 500mA @ 24V)
> Main: ~230V AC ±10%
> Auxiliary: 24V DC / 0.3A
> Backup: 12V / 7Ah battery
> Max Current (with fully charged battery): 700mA
> Standby Current: 125mA
> Operating Temperature: -5°C to +40°C
> Dimensions: 340 x 290 x 100 mm
> Weight: ~2.4 kg (without battery)
> Housing: Plastic enclosure
> Standards: EN54-2/4 certified
> Active end-of-line monitoring
> One-man zone testing
> Multilingual support
> LED indicators
> Security key access.